Technology

Energy-Efficient AAC Home

23.06.2026

Why Private Homebuilders Choose Autoclaved Aerated Concrete: Numbers Over Words

Building your own home from autoclaved aerated concrete (AAC) is a choice increasingly made by those who think about costs not only during construction but also during operation — heating, cooling, and maintenance over the coming decades. And here is why this is not just marketing.

UDK AAC blocks are structural-thermal building products, meaning they have sufficient compressive strength to construct load-bearing walls while also offering excellent thermal insulation properties that meet current thermal resistance standards without additional insulation. UDK AAC blocks with a density of 400 kg/m³ have a thermal conductivity coefficient of λ = 0.1 W/m·°C — a figure confirmed by accredited laboratory test reports. For comparison: solid clay brick has λ = 0.67–0.81 W/m·°C — six to eight times worse. At the same wall thickness, a wall built from UDK autoclaved aerated concrete loses six to eight times less heat than a brick wall.

Choosing the Right AAC Wall Thickness: Calculations by Climate Zone in Ukraine

Ukraine is divided into two climate zones in accordance with DBN B.2.6-31:2021. The zone determines the minimum required thermal resistance of walls (R) and, accordingly, the required block thickness.

The thermal resistance of an envelope structure (R) is directly proportional to the material thickness and inversely proportional to the thermal conductivity coefficient (λ, W/m·°C).

Zone I — Colder Climate (most of Ukraine)

Normative wall R ≥ 4.0 m²·°C/W.
Covers: Kyiv, Kharkiv, Poltava, Chernihiv, Sumy, Dnipropetrovsk, Donetsk, Luhansk, Kirovohrad, Cherkasy, Vinnytsia, Zhytomyr, Khmelnytskyi, Ternopil, Rivne, Volyn, Lviv, Ivano-Frankivsk, Zakarpattia, and Chernivtsi oblasts.

Zone II — Milder Climate (southern Ukraine)

Normative wall R ≥ 3.5 m²·°C/W.
Covers: Odesa, Mykolaiv, Kherson, and Zaporizhzhia oblasts.

UDK AAC block walls 400 mm thick achieve R ≥ 3.5 m²·K/W.
Without additional external insulation, they are suitable for use in both Zone II, where normative thermal insulation requirements for walls are lower (from 3.5 m²·K/W), and Zone I, where requirements are higher (but 80% of 4.0 m²·K/W is permitted).
For the external load-bearing walls of a private home, the recommended block is 400 mm thick. It delivers R = 4.0 m²·°C/W and fully satisfies DBN normative requirements for both climate zones without any additional conditions.

Two climate zones of Ukraine in accordance with DBN B.2.6-31:2021.

Does UDK AAC Need External Insulation?

Short answer: with a 400 mm block — no.
Provided all other envelope structures meet the normative thermal resistance values under DBN, most private homes with UDK AAC block walls 400 mm wide can achieve energy efficiency class “B” or “C” — depending on the number of storeys and overall dimensions — even in the colder Zone I.
Replacing a 400 mm AAC wall with a thinner 300 mm wall plus 100 mm of additional insulation is not economically viable. Cost savings per m² of external wall only arise when using low-quality, highly combustible cheap EPS foam boards with a short effective service life. When a quality, non-combustible 100 mm insulation board is mounted on the façade, a single-layer AAC wall proves less expensive overall.
If the goal is energy class “A”, it is engineering solutions — not necessarily additional insulation — that are added to the wall system.

SolutionEnergy Efficiency ClassWall Service Life
UDK 400 mm without insulationB and above50+ years
UDK 400 mm + heat recovery ventilation + heat pumpA (with a comprehensive design approach)50+ years
Brick 380 mm + mineral wool 100 mmB–C50+ years (wall) / 25–30 (insulation)

The second option is the most cost-effective in the long run. Investment in heat recovery ventilation and a heat pump pays back faster than an additional insulation layer — and does not require replacement after 25–30 years.

How to Achieve Energy Class "A" in an AAC Home: What Actually Makes the Difference

Walls are only part of the equation. A significant share of heat is lost through ventilation, windows, and inefficient building services. Class “A” is achieved through a comprehensive approach — here are five key factors:

  1. Heat recovery ventilation — returns 70–90% of the heat from exhaust air back into the living space. One of the most effective long-term measures.
  2. Heat pump instead of a gas boiler — reduces heating costs by a factor of 3–4. Particularly important given annual increases in gas and electricity tariffs.
  3. Windows — at minimum a double-chamber sealed unit with a low-emissivity coating. Heat losses through windows can account for 25–30% of the overall thermal balance of the building.
  4. Airtightness — air infiltration through gaps increases heating costs by 15–20%. Verified by a Blower Door test after construction is complete.
  5. Building orientation — maximum glazing to the south, minimum to the north. Passive solar gain can cover up to 20% of the heating demand.

Five Common Mistakes When Building an AAC Home

  1. Thick mortar joints between blocks
    Laying with cement-sand mortar at joint thicknesses of 10–15 mm creates thermal bridges that entirely negate the insulating advantages of the material. The rule: use UDK TBM thin-layer adhesive mortar at an average bed joint thickness of 2–3 mm.
  2. Unprepared base for the first course
    The first course is always laid on cement-sand mortar with thorough levelling to a true horizontal plane. Any error at this stage is carried through the entire masonry.
  3. Missing reinforcement in critical zones
    Zones above openings, lintels, and ring beams require reinforcement in accordance with the structural design. Neglecting this requirement creates a risk of cracking in the event of uneven foundation settlement.
  4. Uninsulated floor slab edges
    Reinforced concrete floor slabs bearing on an AAC wall create a thermal bridge. The slab edge must always be insulated — otherwise significant heat loss and a risk of condensation will occur in that zone.
  5. Incorrect window installation
    Windows must not be set flush with the outer face of the wall; instead, they are set back so that the frame is overlapped by the block on the street side by a minimum of 50–60 mm. This eliminates thermal bridges at the window-to-wall junction.

Need Advice on Choosing the Right Block?

UDK blocks are manufactured to DSTU standards and carry CE marking — a certificate of conformity with European standards.

View the full product range, certificates, and test reports

Calculate the required volume of AAC for your project

Frequently Asked Questions About UDK AAC Homes (FAQ)

Does UDK AAC 400 mm need to be insulated?

No. A 400 mm UDK block fully satisfies DBN normative requirements for any region of Ukraine. Additional external wall insulation is not required.

What block sizes does UDK offer and what is each suitable for?

UDK manufactures blocks 100 mm and 150 mm thick — for internal partition walls; 250 mm and 300 mm — for load-bearing walls under certain conditions and structural configurations; 400 mm — the optimum choice for external load-bearing walls, meeting DBN standards without additional conditions. Standard face dimensions: length 600 mm, height 200 mm.

What is the service life of an AAC home?

The mineral structure of autoclaved aerated concrete does not degrade over time. The design service life of the structure is 50–100 years, supported by the track record of buildings in Western Europe erected in the 1970s and 1980s.

Can a two-storey home be built using UDK AAC?

Yes. UDK AAC has a compressive strength of 2.7 MPa and freeze-thaw resistance of F100, allowing the construction of load-bearing walls for multi-storey buildings. The specific structural solution is determined by the design engineer based on the applied loads.

How does AAC perform in fire?

Autoclaved aerated concrete is a non-combustible material, classified as NG (A1 under the European classification). It does not support combustion and does not emit toxic substances. The fire resistance rating of load-bearing AAC structures is REI 120–180, depending on block thickness and applied load.

Are there moisture-related issues in AAC homes?

AAC has an open porous structure and is highly vapour-permeable, which has a positive effect on indoor climate. Key requirements: proper ventilation design and the use of compatible vapour-permeable protective and decorative finishing materials on external wall surfaces.

What mortar system is recommended for UDK blocks?

The manufacturer recommends UDK TBM thin-layer adhesive mortar at a bed joint thickness of 2–3 mm. This eliminates thermal bridges through the joints and ensures maximum thermal homogeneity of the wall construction.

Please confirm you are not a robot
To continue using the website, please complete the security check. This helps us protect the platform from automated requests and ensure a comfortable experience for all visitors.
wp.i18n.setLocaleData( { 'text direction\u0004ltr': [ 'ltr' ] } ); //# sourceURL=wp-i18n-js-after var wpcf7 = { "api": { "root": "https:\/\/udk.ua\/en\/wp-json\/", "namespace": "contact-form-7\/v1" } }; //# sourceURL=contact-form-7-js-before